Bosch fme-420-lsn-ttl LSN improved test tool fire alarm system LSN improved test tool
Distinguish fault detection and location based on LSN and LSN improved fieldbus, professional installation inspection for handover, including basic function test of file peripheral (for sounder and beacon) 33000 HK: fme-420-lsn-ttl test tool to test whether the fieldbus (LSN and LSN improvement) and peripheral components connected to the bus are set correctly and work normally. The LSN and peripheral components in the loop, stub or T-tap, and faults in wiring or components are identified and indicated. LSN fieldbuses belonging to the following panels can be tested with test equipment: Europe CE fme-420-lsn-ttl
Fpa-5000 modular fireproof board
Fpa-1200 fireproof board
· BZ 500 fireproof board
· UEz 2000 pause and security system
· UEz 1000 fire, detention and safety systems
· NZ 300 pause and safety system
· map 5000 pause and security system
Ugm-2020 general security system
System overview:
2 | LSN improved testing tools
3 LSN connection
4 power supply (230 V max)
5 on / off switch
6 USB ports
7 ventilation
function
The test tool has two main functions. First, all components connected to the fieldbus are detected automatically and their properties are displayed. Secondly, resistance measurement detects the divergence of line resistance and contact resistance.
Note that resistance measurements are limited to the loop topology. Stumps cannot be measured.
Detected faults
· short circuit
· creeping shorts
· interruption
· creep interruption
· ground fault
· defective and defective components
· duplicate rotary switch address
The LSN mode is not set correctly
Regional certification
European CE fme-420-lsn-ttl
Parts included
1 LSN improved test device
1 power cable with power plug
1 USB interface cable
1 LSN adapter
5 LSN connection cables with plug-in terminals and alligator clips
1 grounding cable
1 CD with software and drivers
technical specifications
Voltage range 110 to 230 V AC (50 to 60 Hz)
Operating temperature 0 to + 45 ° C (+ 32 to + 113 ° f)
Storage temperature - 25 to + 80 ° C (- 13 to + 176 ° f)
Protection grade IP30
Weighs about 5.5 kg (12 lb)
ordering information
LSN improves test tools